Technical parameters of busbar

Feb 25, 2022

Conditions of Use

Ambient temperature

Upper limit: +40℃

Lower limit: -25℃

Altitude: below 2000m

Humidity: The relative humidity does not exceed 50% when the maximum temperature is +40°C; higher relative humidity is allowed when the temperature is lower

Condensation conditions: yes

Earthquake basic intensity: 6 degrees fortification


Installation Location

Indoors, outdoors


Insulation resistance

The insulation resistance value of each closed busbar unit should be greater than or equal to 100MΩ (2500V megger).


Dielectric strength

Each section of the enclosed busbar is subjected to a 1-minute power frequency dry test withstand voltage test before leaving the factory.

Power frequency withstand voltage and lightning impulse withstand voltage values, in line with national standards.


Grounding system

Meet the requirements of IEC364-5-54 for grounding system.


Protection class

Indoor type: IP40; Outdoor type: IP43, IP55.


Load performance

Under the rated current, the temperature rise of the casing meets the requirements of GB763-90 "Heat of AC High Voltage Electrical Appliances in Long-term Operation".


Short circuit performance

The dynamic and thermal stability test meets the standard requirements of GB2706-89 "Test method for dynamic and thermal stability of AC high-voltage electrical appliances".